Accès gratuit
Numéro |
La Houille Blanche
Numéro 7, Octobre 1994
|
|
---|---|---|
Page(s) | 56 - 66 | |
DOI | https://doi.org/10.1051/lhb/1994077 | |
Publié en ligne | 1 octobre 2009 |
La Houille Blanche, N°7 (Octobre 1994), pp. 56-66
Le réseau de distribution d'eau potable à Paris : mesures de débit in situ, comparaison de débitmètres installés à demeure à des étalons
E.D.F.-D.T.G. Grenoble
Abstract
Drinkable water supply network of Paris : in situ flow measurement, comparison between fixed flowmeters and master instruments Ultrasonic flowmeters setting up for water networks management is difficult. It is necessary to comply with the manufacturer's start up processes. Measure differences were observed when comparing measurement on drinkable water supply network of Paris with E.D.F.-D.T.G. master instruments references. The choice of measure and probes setting up in the pipe is at the origin of the differences.
© Société Hydrotechnique de France, 1994